Installed a return air on package unit that was sitting on the roof to help the negative pressure in the building. We tested the doors and ran an unofficial balance test. The building is much more comfortable now on5/30/24 in Arlington Texas. Near S Collins St Arlington, TX 76018 Check out the Areas We Serve…
Read more
Replaced Failed Compressor
Replaced failed compressor. Recovered refrigerant and replaced filter driers, compressor and contactor and confirmed to be functioning properly on 5/15/24 in Fort Worth Texas. Near 701 Galveston Ave Fort Worth, Texas 76104 Check out the Areas We Serve and jobs we are doing by clicking https://dallas.prorefrigerate.com/areas-we-serve/ [spacer][SHORTCODE_ELEMENTOR id=3540]
Read more
Phase Monitor was Not Working
Phase monitor was not working and seemed to be holding the compressor off. I acquired a new phase monitor and installed it. I started the system up and found a breaker trip on stage to call. I back tracked the failure all the way to the recently replaced stage 2 compressor. This compressor is under…
Read more
Condenser was Off in High Limit
Condenser was off in high limit. Reset condenser and compressor started. Measured all parameters and all are within specs. Condenser fan is cycling off/on. Sight glass is full. Returning glycol at 67 degrees. Supply glycol at 43 degrees. Fan running and clean wheel. Cinder coils clean. Noted storms recently make have induced a power surge…
Read more